BKF Ex-proof Wall Air Conditioner

Explosion protection to

  • CENELEC
  • IEC

Can be used in: Zone 2

Explosion Protection Ratings:

Outdoor Unit:

BYS Compressor: II 3 G Ex nC II 146°C(T3); Ex d nC IIB 146℃

BZC Control station: II 3 G Ex d IIB

BDJ-W Fan motor: II 3 G Ex d IIB

Indoor Unit:

BDJ-N Fan motor: II 2 G Ex d IIB T4

BXK Control station: II 2 G Ex d [ib] ib IIB T4

Whole unit: Ex nC d [ib] ib IIB 146℃; IECEx CQM 08.0017X

Product Parameters

Model: BKF-50/220

  • Cooling capacity: 5275W (18000* BTU)
  • Rated voltage / Frequency: 220-240V/50Hz
  • Input power: 2P
  • Cooling input power / Current: 2300W / 10.5A
  • Application areas(m2): 24-36
  • Sound level(dB): Indoor unit: 43* / Outdoor 54*
  • Outline dimensions (L x W x H):
    • Indoor unit: 960 x 385 x 245 mm
    • Outdoor unit: 873×555×376 mm
    • Control box: 400×450×203 mm
  • Weight: Indoor 21.00 kg / Outdoor 62.00 kg / Control box 21 kg

Model: BKF-71/220

  • Cooling capacity: 7066W (24000* BTU)
  • Rated voltage / Frequency: 220-240V/50Hz
  • Input power: 3P
  • Cooling input power / Current: 3100W / 14.9A
  • Application areas: 29-48 m2
  • Sound level: Indoor 44* dB / Outdoor 55* dB
  • Outline dimensions (L x W x H):
    • Indoor unit: 1075×400×182* mm
    • Outdoor unit: 958×660×402* mm
    • Control box: 400×450×205* mm
  • Weight: Indoor 25.00* kg / Outdoor 65.00* kg / Control box 21 kg