Explosion-proof light Zone 1, metal body SCHUCH-Germany e181/182

5-31-2014 6-07-53 PM

SCHUCH QUALITY - YOUR ADVANTAGE

  • Sturdy design of high chemical resistance for application in rough industrial condition
  • Reliable, fail safe and long-life thanks to a special ex-protected quartz sand encapsulated ECG:
  • With high-grade quality features
  • "End-of-life switching-off system" i.e. at life end the fluorescent tube is safely switched off (worldwide first certification acc. to the latest IEC standards IEC 60079-7 with 2 safety circuits test 1 and test 2)
  • In compliance with the requirements of over voltage category III (standard = over voltage category II)

Applications:

Hazardous areas of Zones 1, 21 and 2, 22, e.g. paint shops, paint-spray linesand spray booths

Housing: Sheet steel, powder coated in white (RAL 9016); stainless steel on request

Glass cover: Impact resistant safety glass pane, frameless / hinged

Reflector: Hinged; white painted sheet steel; detachable

Central locking system: Operated by a 5mm allen key, hinges on the opposite side

Isolating switch: Switching off all poles when light fitting is opened

Optical indicater showing the actual position of the switch

Mounting: Suspension hooks (H8V P) or ceiling brackets (15A P), at extra charge (see accessories)

Wiring: Double channel ballast with “end-of-life switching-off system”

Connection terminals: Standard L1+N+PE, up to 6,0mm2

Cable entries: 3 entries M25 x 1,5 (2 glands,1 of them with plug and 1 screw plug)

LOOP-IN/OUT possible, for some versions temperature resistant cable is required

Through wiring system: 5 x 2,5mm2 through wiring or preparation for 5-pole

LOOP-IN/OUT at extra charge

Standard:

Facing downwards or forwards